Features
- Certified Class I Division 2, Groups A, B, C and D
as per CSA C22.2 No.137-M1981 and Class I,
Zone 2 and (Groups IIC, IIB, IIA)
- Temperature Code: T6 (maximum 85ºC as per
Canadian Electrical Code, Part I and CSA C22.2
No.137-M1981)
- CSA certified, meets or exceeds C860 requirements
- Suitable for cold weather: -20ºC (self-powered
model, “CW” option) and -40ºC (AC-only and
AC-DC models)
- Input voltages: 120 to 347Vac universal AC-input; 6
to 48Vdc universal DC-input
High impact thermoplastic frame, with built-in
gasket to prevent water infiltration
- Suited for areas with the risk of presence of flammable gases, vapours or liquids that could create an
explosive atmosphere
- Sealed face-plate in heavy-duty, vandal-resistant
polycarbonate
- Tamper-resistant, hermetically sealed, magnetic test
switch
- Self-test/self-diagnostic circuitry is standard on
self-powered models
- Sealed, maintenance-free, nickel-cadmium
batteries
- Batteries recharge as per CSA requirements and
provide 90 minutes of emergency operation
- Long-life, energy efficient, AlInGaP red LED light
source
- Energy efficient – consumes less than 3watts in
AC or DC mode
|